Switch actuator REG-K/4×230/16 with manual mode and current detection

Switch actuator REG-K/4×230/16 with manual mode and current detection

Category:

Description

For independent switching of four loads via make contacts. The actuator has integrated current detection that measures the load current on each channel. All 230 V switch outputs can be operated with manual switches. With integrated bus coupling unit.
A green LED indicates that the device is ready for operation once the application has been loaded. The load is connected with screw terminals.
For installation on DIN rails TH35 according to EN 60715. The bus is connected using a bus connecting terminal; a data rail is not necessary.
KNX software functions: Operation as break contact or make contact. Staircase lighting function with/without manual OFF function and switch-off warning. Delay functions. Scenes. Logic function. Blocking or priority control. Feedback function. Status. Central function with delay. Parameterisation for bus voltage failure and recovery. Behaviour for download.
Current detection function: Behaviour when value exceeds/falls short of the threshold value. Energy, operating and switch on counter with limit value monitoring.
Flash function.
Nominal voltage: 230 V AC, 50-60 Hz
DC 12-24 V ±10%, 0.1-16 A
For each switching contact:Switching current: 16 A, cosφ= 0.6
AC1 operation: max. 16 A
AC3 operation: max. 10 A
AC5 operation: max. 16 A
DC current switching capacity: max. 16 A/ 24 V DC
Output life endurance:
Mechanical: >106
AC1/AC3/AC5 operation: >3×104
230V, 1A resistive: >8×105Incandescent lamps: 230 V AC, max. 3600 W
Halogen lamps: 230 V AC, max. 2500 W
Fluorescent lamps: 230 V AC, max. 2500 VA, with parallel compensation
Capacitive load: 230 V AC, 16 A, max. 200 μF
Minimum switching performance: 100 mA/12 V AC/DC
Maximum peak inrush-current:
150μs: 600 A
250μs: 480 A
600μs: 300 A
Current detection load current:Detection range: 0.1 A to 16 A (sine effective value or direct
current)
Detection accuracy: +/- 8% of the present current value (sine) and +/- 100 mA
Frequency: 50/60 Hz with alternating voltage
Display: 100 mA
Device width: 4 modules = approx. 72 mm
Contents: With bus connecting terminal and cable cover.

Shopping Cart
There are no products in the cart!
Continue Shopping