Description
For independent switching of eight loads via make contacts. With integrated bus coupler and plug-in screw terminals.
A green LED indicates readiness for operation after the application has been loaded.
For installation on DIN rails TH35 according to EN 60715. The bus is connected using a bus connecting terminal; a data rail is not necessary.
KNX software functions: Operation as break or make contact, delay functions for each channel, staircase lighting function with/without manual OFF function, cut-out warning for staircase lighting function, blocking and additional logic operation or priority control, scenes, status feedback function per channel, central function, comprehensive parameterisation for bus voltage failure and recovery, parameterisable download behaviour.
Nominal voltage: AC 230 V, 50-60 Hz
For each switching contact:
Nominal current: 6 A, cosφ = 0.6
Incandescent lamps: AC 230 V, max. 1380 W
Halogen lamps: AC 230 V, max. 1380 W
Fluorescent lamps: AC 230 V, max. 1000 VA
Capacitive load: AC 230 V, 6 A, max. 105 μF
Device width: 4 modules = approx. 72 mm
Contents: With bus connecting terminal and cable cover.