Description
For independently switching 8 loads via make contacts. The actuator has integrated current detection that measures the load current on each channel. All 230 V switch outputs can be operated with manual switches. With integrated bus coupling unit.
A green LED indicates that the device is ready for operation once the application has been loaded. The load is connected with screw terminals.
For installation on DIN rails TH35 according to EN 60715. The bus is connected using a bus connecting terminal; a data rail is not necessary.
KNX software functions: Operation as break contact or make contact. Staircase lighting function with/without manual OFF function and switch-off warning. Delay functions. Scenes. Logic function. Blocking or priority control. Feedback function. Status. Central function with delay. Parameterisation for bus voltage failure and recovery. Behaviour for download.
Current detection function: Behaviour when value exceeds/falls short of the threshold value.
Energy, operating and switch on counter with limit value monitoring.
Flash function.
Nominal voltage: AC 100-240 V ±10%
DC 12-24 V, 0.1-16 A
Operating voltage: min. AC 90 V – max. AC 265 V
Mains frequency: 50-60 Hz ±10%
For each switching contact:
Switching current: 16 A, cosφ= 0.6
AC1 operation: max. 16 A
AC3 operation: max. 10 A
AC5 operation: max. 16 A
DC current switching capacity: max. 16 A/ 24 V DC
Output life endurance:
Mechanical: >106
AC1/AC3/AC5 operation: >3×104
230V, 1A resistive: >8×105
Nominal load
Incandescent lamps: AC 100 V, max. 1600 W
AC 230 V, max. 3600 W
AC 240 V, max. 3840 W
Halogen lamps: AC 100 V, max. 1086 W
AC 230 V, max. 2500 W
AC 240 V, max. 2608 W
Fluorescent lamps: AC 100 V, max. 1086 VA
AC 230 V, max. 2500 VA
AC 240 V, max. 2608 VA
parallel-compensated
Capacitive load: AC 230 V, 16 A, max. 200 μF
Motor load: AC 100 V, max. 434 W
AC 230 V, max. 1000 W
AC 240 V, max. 1043 W
Minimum switching performance: 100 mA/12 V AC/DC
Maximum peak inrush-current:
150μs: 600 A
250μs: 480 A
600μs: 300 A
Current detection (load current):
Detection range: 0.1 A to 16 A (sine effective value or DC)
Sensing accuracy: +/- 8% of the current value at hand (sine) and +/- 100 mA
Frequency: 50/60 Hz, for alternating current (AC)
Description: 100 mA
Device width: 8 modules = approx. 144 mm
Contents: With bus connecting terminal and cable cover.