Description
For independent control of up to 8 blind/roller shutter drives or for switching up to 16 loads via make contacts. The function of the blind or switching channels is freely configurable. All blind/ switch outputs can be operated manually using push-buttons.
The bus is connected using a bus connecting terminal; a data rail is not necessary. Channel status display via LEDs. A green LED indicates readiness for operation.
With integrated bus coupler. For installation on DIN rails TH35 according to EN 60715. The bus is connected using a bus connecting terminal; a data rail is not necessary.
KNX software functions: Blind functions: Blind type. Running time. Idle time. Step interval.
Weather alarm. 8-bit positioning for height and slats. Scenes. Status and feedback function.
Switch actuator functions: Operation as break contact/make contact. Programmable behaviour for download. Delay functions for each channel. Staircase lighting function with/without manual OFF function. Cut-out warning for staircase lighting function. Scenes. Central function.
Disable function. Logic operation or priority control. Status feedback function for each channel.
Nominal voltage: AC 100-240 V ±10%
Operating voltage: min. AC 90 V – max. AC 265 V
Mains frequency: 50-60 Hz ±10%
For each blind output:
Nominal current: 10 A, inductive load cosϕ = 0.6
Motor load: AC 100 V, max. 434 W
AC 230 V, max. 1000 W
AC 240 V, max. 1043 W
For each switch output:
Nominal current: 10 A, ohmic load cosϕ = 1
10 A, inductive load cosϕ = 0.6
Nominal load
Incandescent lamps: AC 100 V, max. 869 W
AC 230 V, max. 2000 W
AC 240 V, max. 2086 W
Halogen lamps: AC 100 V, max. 739 W
AC 230 V, max. 1700 W
AC 240 V, max. 1773 W
Fluorescent lamps: AC 100 V, max. 434 VA
AC 230 V, max. 1000 VA
AC 240 V, max. 1043 VA
parallel-compensated
Capacitive load: AC 230 V, 10 A, max. 105 μF
External auxiliary voltage (optional):
Nominal voltage: AC 110-240 V ±10%
Operating voltage: min. AC 92 V – max. AC 265 V
Device width: 8 modules = approx. 144 mm
Note: The blind actuator/switch actuator cannot be used in conjunction with the weatherdependent
automatic functions of the weather combi-sensor/DCF77 art. no. MTN663692. If
you require these functions then use the blind actuators art. no. MTN6498…
Contents: With bus connecting terminal and cable cover.