Description
To buffer the bus voltage. If a complete mains failure occurs, an external lead gel battery
with a voltage of DC 12 V (SELV) can be connected to the REG power supply for buffering.
The lead gel battery is recharged or maintained in its charged state by integrated charging
electronics.
A binary input can be connected in order to register the operational statuses (mains voltage, error warning, battery operation).
For installation on DIN rails TH35 according to EN 60715. A data rail is not necessary.
Nominal voltage: AC 110-230 V ±10%
Operating voltage: min. AC 92 V – max. AC 253 V
Mains frequency: 50-60 Hz ±10%
Output to power supply:
Output voltage: DC 30 V ±2 V
Output current: without battery with mains supply max. 300 mA, with battery without mains supply max. 640 mA
Buffer time with lead gel battery 7,2 Ah:
683890: approx. 0.5 h
683832: approx. 1 h
683816: approx. 2 h
Buffer time with lead gel battery 18 Ah:
683890: approx. 1.25 h
683832: approx. 2.5 h
683816: approx. 5 h
Short-circuit current: < 1.5 A
Charging current: max. 1 A
Connections: plug-in screw terminal for main connector, operating state (4-pin, 3 floating contacts)
and emergency power supply. Plug-in terminal for battery connection (two 1 mm pins)
Device width: 4 modules = approx. 72 mm
In KNX, to be completed with: KNX power supply REG-K/160 mA with emergency power input MTN683816
KNX power supply REG-K/320 mA with emergency power input MTN683832
KNX power supply REG-K/640 mA with emergency power input MTN683890
Accessories: Lead gel battery MTN668990
MTN668991
Binary input REG-K/4×24 MTN644892
Spannungsversorgung REG, DC 24 V/0,4 A MTN693003
Contents: With connecting terminal and cable cover